# 48283B006 Page 1
Save these instructions for future reference
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
2SCU13 Series
Split System Air Conditioner
Sharp metal edges can cause injury. When
installing the unit, use care to avoid sharp
edges.
WARNING
Installation and servicing of air conditioning
equipment can be hazardous due to internal
refrigerant pressure and live electrical com-
ponents. Only trained and qualified service
personnel should install or service this equip-
ment. Installation and service performed by
unqualified persons can result in property
damage, personal injury, or death.
WARNING
Risk of electrical shock. Disconnect all
remote power supplies before installing or
servicing any portion of the system. Failure
to disconnect power supplies can result in
property damage, personal injury, or death.
WARNING
The equipment covered in this manual is to be installed by trained and experienced
service and installation technicians. Improper installation, modification, service, or
use can cause electrical shock, fire, explosion, or other conditions which may cause
personal injury, death, or property damage. Use appropriate safety gear including
safety glasses and gloves when installing this equipment.
WARNING
Manufactured By
A.A.C.
A Lennox International Inc. Company
421 Monroe Street
Bellevue, OH 44811
TABLE OF CONTENTS
INSTALLATION ...................................... 2
START-UP ............................................ 10
OPERATION ........................................ 14
MAINTENANCE ................................... 14
CONNECTION DIAGRAMS ................. 16
WARRANTY ......................................... 18
*48283B006*
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - *48283B006*

# 48283B006 Page 1Save these instructions for future referenceINSTALLATION AND MAINTENANCEINSTRUCTIONS2SCU13 SeriesSplit System Air ConditionerSharp m

Page 2 - Torque Table

Page 10 # 48283B006If the system is void of refrigerant, clean the system usingthe procedure described below.1. Use dry nitrogen to pressurize the sys

Page 3 - Indoor Blower

# 48283B006 Page 11Charge Using Weigh-In Method (Fixed Orifice/TXVSystems)If the system is void of refrigerant, or if the outdoor ambienttemperature i

Page 4 - Figure 5

Page 12 # 48283B006Pressures higher than those listed indicate that thesystem is overcharged. Pressures lower than thoselisted indicate that the syste

Page 5 - Figure 7

# 48283B006 Page 13Normal Operating PressuresTable 9lioCroodtuOriAgniretnEerutarepmeTledoM81- 42- 03- 63- 24- 84- 06-L S L S L S L S L S L S L S)VXT(e

Page 6 - Figure 8

Page 14 # 48283B006OPERATIONOutdoor unit and indoor blower cycle on demand from theroom thermostat. When the thermostat blower switch ismoved to the O

Page 7

# 48283B006 Page 155. Check for correct voltage at unit (with unit operating).6. Check amp-draw on blower motor.Unit nameplate _________ Actual _____

Page 8

Page 16 # 48283B006Figure 12HCF1DESCRIPTIONKEY COMPONENTA4 CONTROL - TIMED OFFB1 COMPRESSORB4 MOTOR - OUTDOOR FANC12 CAPACITOR - DUALHR1 HEATER - COMP

Page 9

# 48283B006 Page 17Figure 13Three Phase Wiring Diagram P/N 48436-001B4OUTDOORFANC1OUTDOOR FANCAPACITORA4TIMED OFFCONTROL(IF USED)PURPLEBLACKORANGEBLAC

Page 10 - .ni8/3.tf5rep.zo3

Page 18 # 48283B006Limited WarrantyAugust 1, 1997This warranty gives you specific legal rights and you may have other rightswhich vary from state/prov

Page 11 - Fixed Orifice or TXV Systems

Page 2 # 48283B006INSTALLATIONLocation of UnitOutdoor units operate under a wide range of weatherconditions; therefore, multiple factors must be consi

Page 12 - 601119558

# 48283B006 Page 3Figure 2Slab Mounting2° or 2" per 5' slope tolerance away from buildingstructure.Discharge AirMounting SlabGround LevelBui

Page 13 - Normal Operating Pressures

Page 4 # 48283B006Table 2Refrigerant Line Set Diameters (in.)For installations exceeding 50', contactTechnical Services at (419) 483-4840.eniLnoi

Page 14

# 48283B006 Page 5Figure 6To hang line set from joist or rafter,use either metal strapping materialor anchored heavy nylon wire ties.Strapping Materi

Page 15

Page 6 # 48283B006Figure 8Refrigerant Line Sets: Installing Vertical Runs (new construction shown)Outside WallWood BlockBetween StudsIMPORTANT: Refrig

Page 16 - Figure 12

# 48283B006 Page 7To install an expansion valve (see Figure 9):1. Separate the distributor assembly and remove thepiston orifice and used teflon seal.

Page 17 - # 48283B006 Page 17

Page 8 # 48283B006To Close Liquid or Suction Line Service Valve:1. Remove the stem cap with an adjustable wrench.2. Use a service wrench with a hex-he

Page 18 - Limited Warranty

# 48283B006 Page 95. Evacuate the line set and indoor unit to a minimum of 500microns or lower. During the early stages of evacuation, itis desirable